NVD

Id
88012  
Name
CVE-2017-6030  
Description
A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.  
Reject
 
CVSS Version
2  
CVSS Score
6.4  
Severity
Medium  
CVSS Base Score
6.4  
CVSS Impact Subscore
4.9  
CVSS Exploit Subscore
10  
CVSS Vector
(AV:N/AC:L/Au:N/C:P/I:N/A:P)  
Pub Date
2017-07-18  
Published
2017-06-29  
Modified Date
2017-07-07  
Seq
2017-6030  

Actions