NVD

Id
45772  
Name
CVE-2012-4359  
Description
Sielco Sistemi Winlog Pro SCADA before 2.07.18 and Winlog Lite SCADA before 2.07.18 do not validate the return value of the realloc function, which allows remote attackers to cause a denial of service (invalid 0x00 write operation and daemon crash) or possibly have unspecified other impact via a port-46824 TCP packet with a crafted negative integer after the opcode. NOTE: this vulnerability exists because of an incomplete fix for CVE-2012-4358.  
Reject
 
CVSS Version
2  
CVSS Score
9.3  
Severity
High  
CVSS Base Score
9.3  
CVSS Impact Subscore
10  
CVSS Exploit Subscore
8.6  
CVSS Vector
(AV:N/AC:M/Au:N/C:C/I:C/A:C)  
Pub Date
2017-01-19  
Published
2012-08-19  
Modified Date
2012-08-20  
Seq
2012-4359  